4/12
Schneider Electric
44
Quantum automation platform 4
I/O architectures
Distributed I/O, Modbus Plus
Drop interface characteristics
Model 140 CRA 211 10 140CRA21210 140 CRA 211 20 140CRA21220
Function DIO dropinterface
a source voltage
DIO dropinterface
a source voltage
DIO dropinterface
c source voltage
DIO dropinterface
c source voltage
Cable connections
Single Redundant Single Redundant
Input voltage
a 85 … 276 V a 85 … 276 V c 20 … 30 V
Frequency range Hz 47 … 63 47 … 63 –
Input current A 0.4 @ a 115 V
0.2 @ a 230 V
0.4 @ a 115 V
0.2 @ a 230 V
1.6
Inrush current A 10 @ a 115 V
20 @ a 230 V
10 @ a 115 V
20 @ a 230 V
30
Power input VA 50 50 –
Buffer time cycle 0.5 @ full load and minimum line
voltage/frequency and less than 1 s
between interrupts
Max. 1.0 ms
Fusing A 1.5 external 1.5 external 2.5 external
Bus output Voltage c 5.1 V
Current A 3
Minimum load A 0
Protection Over-current, over-voltage
Words
30 I / 32 O (two additional input words are reserved for I/O drop status)
Diagnostics startup
RAM Yes
RAM Address Yes
Checksum Yes
Processor –
Run time
RAM Yes
RAM Address Yes
Checksum Yes
Processor –
Field wiring
Terminal block, 7-pole
Power dissipation
W 11
Characteristics