4/22
Schneider Electric
4
Characteristics
Model 140 CHS 110 00
Comm ports
2 connectors (transmit and receive) for fiber optic link
RFI immunity (per IEC 801-3)
MHz 27 ... 1000, 10 V/m
Bus current
mA 700 (typical)
Electrostatic discharge (per IEC 801-2)
kV 8 air, 4 contact
Compatibility
Software
ProWORX NxT V2.0 or Concept Version 2.0 and or greater
Quantum CPUs
Version 2.0 or higher
Input/output type
Quantum, 800 Series, and Sy/Max (remote I/O only)
Fiber optic ports
1 Transmit
1Receive
Programming software
ProWORX NxT V2.0 or Concept Version 2.0 and or greater
Quantum controllers
All, 984 ladder logic; IEC, 140 CPU 434 12A and 534 14A
CHS loadable software requirements
Version 2.0 minimum
Loadable function block performance
CHS block (Included with kit)
Switchover time
ms 13 to 48 for hot standby to assume control after primary fault detected
Scan impact communications
ms 3 + 6 per kB of configured state RAM
CHS communications rate
10 megabaud
Cable between Quantum systems
m 3 fiber optic
Current requirements
mA 700
Quantum automation platform 4
Hot standby modules
Characteristics
0
Comentarios a estos manuales