Configuring an M1 CPU with Modsoft
172
870 USE 101 00 V.2.2
Changing the Baud Rate
Overview
Each port can be configured for a baud in the range 50...19,200. Sixteen valid
bauds are user-selectable. The factory-set default is 9600 baud.
Note:
If you use a baud rate lower than 4800, you should adjust the default delay
parameter. See Changing the Delay
.
Procedure
To change the baud parameter, perform the steps in the following table.
Step Action
1 Place the cursor on the current Baud entry for the Modbus port you want to enter.
Push
<Enter>
.
Result:
A popup window appears in the top left corner of the screen displaying 16
baud values:
2 Use an arrow key to toggle the cursor onto the desired Baud selection in the popup
window, then push
<Enter>
.
Result:
The Port editor screen is updated with the Baud number you have specified,
and the cursor moves to the Head-Slot column.
Vista de pagina 183