Momentum Modbus Plus 170 PNT Series Guía de usuario Pagina 234

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 373
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 233
Using Peer Cop with Modsoft
222
870 USE 101 00 V.2.2
Specifying References for Input and Output Data,
Continued
Defining the
Specific Output,
Continued
Continued on next page
Step Action
3 In the LEN column of the SPECIFIC OUTPUT field, type the value
8
, indicating that
the the M1 CPU at address 2 will send eight 16-bit words to the supervisory PLC.
Push
<Enter>
.
Result:
The Peer Cop screen should like this:
Vista de pagina 233
1 2 ... 229 230 231 232 233 234 235 236 237 238 239 ... 372 373

Comentarios a estos manuales

Sin comentarios