Using Peer Cop with Modsoft
870 USE 101 00 V.2.2
211
Accessing the Remaining Devices,
Continued
Procedure,
Continued
Next Step
You are now ready to configure Peer Cop for the device at Modbus Plus address 3,
which for this example is a 170 ADO 340 00 16-point output module.
Step Action
4 Enter the value
3
in the Node field. Push
<Enter>
.
Result:
The Add Node popup disappears, and the Peer Cop summary information
values are set as follows: