Using the Ethernet Port
154
870USE10110 July 2004
Cabling Schemes for Ethernet Networks with Momentum Components
Introduction In a standard Ethernet cabling scheme, each device connects via a cable to a port
on a central Ethernet hub.
Length The maximum length of cable between devices depends on the type of hub used,
as shown in the following table.
Cabling with
Traditional Hubs
The following illustration shows the maximum number of hubs and the maximum
cable length between devices when using traditional (non-switching) hubs.
Type of Hub Max. Cable from
Device to Hub
Max. Hubs Between
Any Two Nodes
Max. Cable Between Most
Distant Nodes on Network
Traditional
(Non-switching)
100 m 4 500 m
Switches 100 m Unlimited Unlimited
Note: 10/100 hubs/switches can be used. This will allow 100 Base T networks to
use the M1E.
Cabling with
Traditional Hubs
Hub Hub
I/O Device I/O Device I/O Device I/O Device
500m (1630 ft) Maximum Cable Length
Within the Same Collision Domain
M1E M1E