Saving to Flash
870USE10110 July 2004 253
Saving to Flash in Modsoft for Momentum Components
Conditions for
Saving to Flash
In order to save the application program and state RAM values to Flash:
The Modsoft panel must be Online
The PLC must be stopped (not solving logic)
Save-to-Flash
Procedure
Follow the steps below to save to Flash.
Step Action
1 With the PLC online, go to the Ladder diagram editor or the Segment Status Display.
2 From the PlcOps pull-down on the top menu, select Save to Flash.
Result: If the PLC is stopped when you select Save to Flash, the following screen
appears:
3 Answer the first two questions to specify the way you want the PLC to restart after a
power-down.
PlcOps Elements Edit Go/Srch Network
#00100
Refs Tools
F1
F6
F7 F8 ONLev 8
Seg. 1 #
Utility
000014
000014
00
Format :Binary Online Range : 1
Start [CTRL F5]
Flash RAM Loading Options
Continue Power Down Run State? (Y/N)
Start PLC After Download? (Y/N)
Continue ? (Y/N) N
Optimize Mode
Save to Flash