Setting up the Time-of-Day Clock on Momentum Components with Concept
Overview Each option adapter has a time-of-day clock. To use this feature, you must reserve
a block of eight 4x registers.
This section describes how to reserve those registers, using Concept.
Reserving
Registers for the
TOD Clock
To reserve registers for the TOD clock, perform the steps in the following table
Step Action
1 From the Configure menu, select Specials... OR double-click on any field in the
Specials region of the dialog box. The Specials dialog box appears.
Battery Coil
Timer Register
Time of Day
0x
4x
4x -400007
1536
1872
1865
Allow Duplicate Coils (LL984 only)
Watchdog Timeout (ms*10):
Online Editing Timeslice (ms):
30
20
OK Cancel Help