Configuring a Modbus Plus Network in Modsoft with Peer Cop
870USE10110 July 2004 245
Next Step Defining references for the supervisory computer (see p. 246).
4 Type the value 4 in the INDEX column of the GLOBAL INPUT field, indicating that
the M1 CPU at Modbus Plus address 3 will receive the seven words of global data
starting with word 4.
Result: The Peer Cop screen is now set to send 16 words of specific output to the
supervisor at Modbus Plus address 1 and to receive seven words of global data from
the supervisor. The screen should like this:
Step Action
Utility
GoToNode
AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 500 ms Total Links: Link Id:1
PEER COP
On Error : CLEAR USED 18 OF 2000 WORDS
REFERENCE LEN TYPE INDEXMODE
F2
Timeout
Access to Node : 1
TO ALL NODES ON LINK
GLOBAL OUTPUT -
DelNode
SPECIFIC INPUT -
SPECIFIC OUTPUT 400024-400039 16 BIN
GLOBAL INPUT 400001-400007 7 BIN 4
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -