Editing the I/OBus I/O Map for Components Using Concept
Overview The maximum number of modules which can be I/O mapped on the I/O bus network
depends on your processor adapter and its executive.
Processor Adapter Executive Max. Modules Max. I/O Bits
171 CCS 760 00 984 128 2048
IEC 44 1408
171 CCC 760 10 984 128 2048
IEC 44 1408
171 CCC 960 20 984 256 4069
IEC 128 1408
171 CCC 960 30 984 256 4096
IEC 128 1408