870USE10110 July 2004 31
Chemical Interactions Enclosures and bezels are made of Lexan, a polycarbonate that
can be damaged by strong alkaline solutions
Altitude, Full Operation 2000 m (6500 ft)
Vibration 10 ... 57 Hz @ 0.075 mm displacement amplitude
57...150 Hz @ 1 g
Ref. IEC 68-2-6 FC
Shock +/-15 g peak, 11 ms, half sine wave
Ref. IEC 68-2-27 EA
RFI Susceptibility/
Immunity
Meets CE mark requirements for open equipment.
Open equipment should be installed in an industry-standard
enclosure, with access restricted to qualified service personnel.
Storage Conditions
Temperature -40 ... +85 degrees C
Humidity 5 ... 95% (noncondensing)
Safety Parameters
Degree of Protection Unintentional access (UL 508 Type 1, NEMA250 Type 1, IP20
conforming to IEC529)
Di-electric Strength RS232 and I/OBus are non-isolated from logic common
Ground Continuity 30 A test on the exposed metal connector
Agency Approvals UL 508, CSA, CUL, CE; FM class1, div2