Momentum Modbus Plus 170 PNT Series Guía de usuario Pagina 33

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 376
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 32
Overview of Momentum M1 Processor Adapters
870USE10110 July 2004 33
LED Indicators This processor adapter has two LED indicators, RUN and COM ACT. Their functions
are described in the table below:
Specifications The following table contains specifications for the 171 CCS 760 00 Momentum M1
processor adapter:
LED Status Function
Start up Both Single flash. Indicates good health.
RUN Green On continuously when the CPU has received power and is solving
logic.
Flashes an error pattern if the CPU is in kernel mode (see p. 367)
Off CPU is not powered up or is not solving logic.
COM ACT Green May be on continuously or blinking. Indicates activity on Modbus port
1.
Off No activity on Modbus port 1.
Memory
Internal Memory 256K bytes
User Memory 12K words
Flash RAM 256K bytes
Clock Speed 20 MHz
Input and Output References
Registers 4096
Discretes 2048 (any combination of 0x and 1x references)
I/O Servicing
Local I/O Services all the points on any host Momentum I/O base
Watchdog Timeout 419 ms
Logic Solve Time 0.25 ms/k ladder logic instructions
Mechanical
Weight 42.5 g (1.5 oz)
Dimensions (HxDxW) 25.9x61.02x125 mm
(1.01 x 2.37 x 4.86 in)
Material (Enclosures/
Bezels)
Lexan
Operating Conditions
Temperature 0 ... 60 degrees C
Humidity 5 ... 95% (noncondensing)