Configuring an M1 CPU with Modsoft
870USE10110 July 2004 199
Changing the Baud Rate on Modbus Communication Ports for Momentum
Components Using Modsoft
Overview Each port can be configured for a baud in the range 50...19,200. Sixteen valid bauds
are user-selectable. The factory-set default is 9600 baud.
Procedure To change the baud parameter, perform the steps in the following table.
Note: If you use a baud rate lower than 4800, you should adjust the default delay
parameter. See Changing the Delay Parameter on Modbus Communication Ports
for Momentum Components Using Modsoft, p. 201
Step Action
1 Place the cursor on the current Baud entry for the Modbus port you want to enter.
Push <Enter>.
Result: A popup window appears in the top left corner of the screen displaying 16
baud values.
2 Use an arrow key to toggle the cursor onto the desired baud selection in the popup
window, then push <Enter>.
Result: The Port editor screen is updated with the baud number you have specified,
and the cursor moves to the head-slot column.
A
Auto
MS-DOS Prompt - COMMAND
Utility
Default
Bridge Quit
F1
EST
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
PORTS Bridge Mode: N
Mode Data Parity Stop Baud Head-Slot Address Delay Protocol
Bits Bits
ASCII 7 ODD 1 9600 0 1 10ms
RTU 8 EVEN 1 9600 0 1 10ms RS232
50
75
110
134
150
300
600
1200
1800
2000
2400
3600
4800
7200
9600
19200